BA 9054/331

Battery symmetry monitor

BA 9054/331

Contacts

Nominal voltage

Start up delay

Measuring range

Switching delay

Approval

Variant

  • 0056172
  • BA9054/331 DC0,12-1,2V UH DC24-60V
Monitoring of battery systems to find voltage inversions of single cells, internal short... more

Product description

Monitoring of battery systems to find voltage inversions of single cells, internal short circuits and sulphating.
The middle connection of a Battery system is connected to terminal “M” of the BA 9054/331. If the two parts of the voltage differ more then the adjusted value for 10 s, the output relay trips. It trips also on broken wire on terminal “M”. The test button allows a test of the unit. It has to be pressed for at least 10 sec.

Technical specifications

Width: 45 mm
Operate delay: Yes
1- / 3-phase: 1
Auxiliary voltage: Without
Output contacts: 2 Wechsler
Enclosure design: Switch cabinet
Type: BA 9054/331

Features

  • According to IEC/EN 60 255-1
  • To monitor for battery systems (emergency power supply)
  • Measuring rang DC 0.12 ... 1.2 V or 0.2 ... 2 V
  • Goldplated contacts to switch low loads
  • High overload possible
  • With time delay 10 s
  • LED indicators for operation and contact position
  • Width: 45 mm
  • For battery voltages up to 300 V
  • Without separately auxiliary voltage
  • 2 changeover contacts